Over 30 years of industrial process experience
Istanbul, Türkiye
SearchRequest a quote
ELS R / Rotary paddle level switch

ELS R Rotary Paddle Level Sensor

Full, empty and intermediate level detection in powders and granules. Product information, stock and technical support for ELS R1 230 VAC and ELS R2 24 VDC versions.

ELS R Rotary Paddle Level Sensor

ELS R is a rotary paddle level sensor that detects when powder or granular material reaches a defined level in silos, hoppers and vessels. It provides full, empty or intermediate level information; it does not measure continuous level height, fill percentage or volume.

We provide product information, stock checks and application-specific technical support for ELS R1 230 VAC and ELS R2 24 VDC. Specify the model, supply and quantity in your quotation request.

Difference between ELS R1 and ELS R2

ModelOur supply optionSelection
ELS R1230 VAC · 50/60 HzPanels with a suitable 230 V AC supply
ELS R224 VDCPanels with a suitable 24 V DC supply

The primary choice between the two models depends on the panel supply. Do not assume a single device operates on both 230 VAC and 24 VDC. When replacing a sensor, check the nameplate and wiring diagram.

How does it work?

The motor rotates the sensing paddle. When material prevents rotation, the mechanism actuates a microswitch and generates a level signal. Once material recedes and releases the paddle, the sensor returns to its initial state.

The SPDT contact output transmits the full/empty signal required by the application to the automation system. Control and alarm logic are configured to suit the plant.

For which applications is it considered?

Measuring pointExample requirement
Upper level in a silo or hopperHigh-level information during filling
Feed hopper low levelWarning when material runs low or the vessel is empty
Intermediate level pointLevel information for managing feed and filling sequences

Example applications include grain and feed, plastic granules, wood chips and other forest products, and building material processes. Suitability is assessed together with material density, particle size, adhesion and mechanical loads.

Mounting and sensitivity selection

The standard sensor can be mounted from above or from the side at the target level. Maintain free paddle rotation; consider a protective arrangement against direct filling impact and high mechanical loads.

Three spring-force settings are available: light, medium and strong. Adjust according to material behavior and the technical documentation. The manual specifies extended versions for full-level detection only; extension and mounting suitability must be checked separately.

Technical documents

ELS R · Turkish product brochureDownload document ↓ELS R · Technical and installation document (English)Download document ↓

When is it suitable?

Considered when detecting whether solids have reached or fallen below a specific level. ELS R1 230 VAC or ELS R2 24 VDC is selected together with the panel supply.

Technical selection and configuration

ELS R1 supply230 VAC · 50/60 Hz
ELS R2 supply24 VDC
Measurement typePoint level / limit detection
OutputSPDT microswitch contact
Housing / protectionAluminum housing · IP66 with correct installation and sealing
Process connectionG 1½″ / G 2½″ according to the brochure; confirm with the actual product
Standard shaft130 mm, stainless steel, according to the brochure
Process temperature−25…+80 °C according to the Turkish brochure
Maximum process pressure+0,8 bar
Material density / particle size>100 g/l / <50 mm according to the technical documentation
Paddle speed1 rpm
Spring-force adjustmentLight / medium / strong

Confirm numeric limits and connection options against the current manufacturer datasheet and exact order code.

Installation notes

Install with the cable entry facing down and seal using suitable glands; close unused entries. Check the process connection, paddle clearance and mechanical loads. Qualified technical personnel must wire the device according to the relevant R1 or R2 diagram.

Conformity documents

The supplied technical document includes the EU declaration of conformity for the ELS-R series. As it does not state ATEX compliance, the product is not offered as ATEX-certified. For special site requirements, the nameplate and relevant documents are assessed together.

Should I choose ELS R1 or ELS R2?

Consider ELS R1 for a 230 VAC supply and ELS R2 for a 24 VDC supply. Final selection includes checking the nameplate and panel connection.

Does it provide continuous level or fill percentage?

No. The sensor detects material at its mounting point and provides a contact output.

Information for a quotation

Provide the R1 or R2 model, supply, quantity, material name, mounting direction and required shaft length. Nameplate and installation photos are also helpful when replacing a device.

What are stock availability and lead time?

Stock quantity and lead time are confirmed at quotation stage for the requested model and quantity.

Related solution area