MOLLET · MOLOSbob · CONTINUOUS LEVEL MEASUREMENT
MOLLET LF20 electromechanical level measurement
Electromechanical tape-based measuring system that lowers a sensing weight to the material surface to determine the level in silos and bunkers.
- Measurement task
- Continuous level
- Measuring principle
- Tape with sensing weight
- Measuring distance
- Up to 42 m
Select measuring distance, scraper, power supply, temperature, sensing weight and ATEX option below.


TECHNICAL PRESELECTION
LF20 configuration for your application
Only standard options confirmed in MOLLET’s published selection document are shown. The resulting code requires technical review before quotation.
Certification / ATEX
?
Hover over or tap the question mark for details about an option.
Add application notes
How does LF20 measure?
A sensing weight is lowered into the silo on a stainless steel tape. When contact with the material surface is detected, the travel distance is determined, the weight is retracted and the current level is sent to the control system as a 4–20 mA signal.


Technical specifications
| Measuring distance | 0–42 m; depending on selected measuring tape |
| Measurement accuracy | ±2,5 cm |
| Output | 4–20 mA; option for up to 4 programmable relay outputs |
| Supply voltage options | 90–253 V AC, 50/60 Hz or 20–28 V DC |
| Process temperature | −20…+150 °C; depending on option |
| Process pressure | −0,5…+1,0 bar |
| Process connection | DN100 PN16 / 4-inch aluminium flange |
| Protection | IP67; product page lists IP67 / IP66 variants |
The values are based on the MOLLET LF20 product page and published quotation information. Special options require manufacturer confirmation.
ATEX and safety
For ATEX, confirm the final selection against the device nameplate, current certificate and the plant’s explosion protection document. Some high-temperature, climate, sensing-weight and accessory options cannot be combined in an ATEX configuration.
Checks for LF20 selection
- Measuring distance: Consider the top connection and free space as well as the silo height.
- Sensing weight: Powder, granules, light materials, interfaces and liquids require different sensing weights.
- Vertical installation: The manufacturer specifies a maximum tilt of 2°; check the mounting surface.
- Operation during filling: Consider an interlock and process sequence to keep the weight out of the filling stream.
- Temperature and scraper: The +150 °C option is only considered with a 500 mm scraper.
Let us verify the silo dimensions together
Share the material, silo height, connection size, temperature, Ex zone and control requirements.