The QV sleeve closes when control pressure is applied and opens when pressure is removed. Do not assume that a bare QV closes on air loss. The solenoid and control arrangement in SFA-Q can behave differently on power loss; adequate control air remains necessary.
Understand the operating principle visually
Diagrams explain the principle; they are not scaled installation or electrical wiring drawings.
Close command · air available
Control pressure compresses the sleeve and closes the passage. Releasing pressure opens the sleeve; the normal position depends on the control command.
Power lost · air available
In the SFA-Q control arrangement, the de-energised solenoid can provide closure. Verify sufficient control air and the complete circuit; do not assume automatic closure for a bare QV valve.
Control air lost
QV opens when sleeve pressure is released. The plant automation must separately define how filling stops upon loss of air.
Assess power loss and air loss separately. Before restarting, check valve status, level, pressure and connection permissions.
Check three separate conditions
| State | What to check |
| Power loss | De-energized solenoid position and available control air |
| Control-air loss | QV opens as sleeve pressure is released; design the system stop sequence separately |
| Restart | Verify level, pressure, connection permission and valve position |
Pressure and sleeve selection
The QV-FF manufacturer page requires control pressure 2.5 bar above process pressure. This does not define one maximum pressure for all valve variants; verify diameter, sleeve, temperature and connection together.