During pneumatic tanker filling, incoming material must stop when the silo is full. Filter performance and silo pressure also require monitoring. A level switch alone does not close the filling line; sensor data, control logic and a physical shutoff element work together.
MOLLET MOLOSsafe SSS integrates maximum-level detection, pressure monitoring, filling valve, controller and warnings. SFA is the filling-line valve; SEI mechanically relieves overpressure and vacuum. These functions do not replace each other.
Component roles
| Requirement | MOLLET solution | Task |
| Integrated filling protection | MOLOSsafe SSS | Combines sensor, valve, control and warning components |
| Filling-line shutoff | SFA-Q or SFA-K | Physically closes the filling connection |
| Pressure monitoring | MOLOSpressdec MSD | Provides a signal based on pressure limit or measured value |
| Pressure / vacuum relief | MOLOSsafe SEI | Provides mechanical relief |
| Operator warning | S-EST and HL / HP | Manages filling logic and provides audible/visual indication |
Hose connection and filling authorization
Detecting an attached hose and identifying the correct filling line are separate tasks. Select connection monitoring or coded couplings according to silo count, material routing and existing connections.
Define filling authorization, level/pressure alarms, power/control-air loss and restart conditions together. Because a pinch valve can reopen when control pressure is removed, assess its behavior in the plant shutdown scenario. Verify authorization, alarms and shutdown during commissioning using manufacturer instructions and the plant test plan.
What information is needed before quotation?
Review silo count and mechanical limits, tanker filling pressure, connection and pipe diameter, filter and relief arrangement, maximum level point, power/control air, ATEX zone and filling-stop method together.
Define authorization, alarm, stop and restart behavior through site risk assessment. Verify SEI relief capacity, valve and sensor selection for the silo project.
Continue selection
Sources
Does a maximum-level sensor alone prevent overfilling?
The sensor generates a warning. Stopping material entry requires suitable logic and a filling-line shutoff element.
Does SEI replace a pressure sensor?
No. SEI provides mechanical pressure/vacuum relief; MOLOSpressdec monitors pressure and provides a signal.