Full signal before the silo is full: what to check?

A check guide for filling impact, deposits and paddle placement on MOLLET DF sensors.

Silo dolmadan “dolu” sinyali geliyor: Ne kontrol edilir?

Photo shows an example configuration. Connection, housing and paddle options vary by order code.

What is the problem?

The level switch reports full as filling starts, although material has not reached the target level. Filling material striking the paddle or deposits around it can produce an effect similar to a real full condition.

Which product addresses it?

For compact sensors such as MOLLET DF21/DF23, check the mounting point and free paddle movement. If the detection point needs to extend further into the silo, assess the DF28 protecting-tube design with verified mounting orientation and mechanical loads.

Full signal before the silo is full: what to check?
DF28 protecting-tube sensor: an example of extending the detection point; length and mounting position are selected for the application.
View the product →
  1. 1 · Filling stream
  2. 2 · Detection point protected from impact
  3. 3 · Free operating area of the paddle
Conceptual diagram, not a scaled installation drawing.

On-site check sequence

1 · Compare alarm timing with filling. Record whether it occurs during filling impact, after filling stops or continuously.

2 · Under safe shutdown conditions, inspect free paddle movement, deposits and mechanical damage. Authorized personnel must perform maintenance and electrical checks according to manufacturer instructions.

3 · Select a position away from direct filling impact. Choose protection and paddle geometry together with material density, connection opening and loads, then repeat empty/full functional tests.

Limits of the solution

A PLC delay can filter brief transients; it does not fix a jammed paddle or incorrect installation. Overfill protection delays and stop logic must be determined for the plant safety scenario.

Send for technical support

Share the device label, paddle photo, silo/filling-pipe layout, material name and alarm timing.