The modified triboelectric principle evaluates signals from particles passing around and striking the sensor.
Select switching or analog output according to alarm or trend requirements. This product is not a flow meter measuring kg/h in a solids feed line.
Leak detection at the filter outlet
Monitors dust passage on the filter's clean-gas side. Signals from particles striking or passing near the sensor rod are evaluated. Signal damping can reduce false alarms caused by filter-cleaning pulses.
The relay version provides alarms; the analog version enables PLC trend monitoring and multiple thresholds. Damping is specified as 0–10 s for the relay version and 0–60 s for the analog version.
Sensor length and installation
The manufacturer recommends a sensor rod length of about one-third to two-thirds of the duct diameter, up to 800 mm. Plan straight inlet and outlet lengths away from bends or valves; the document specifies at least three duct diameters.
Consider threaded socket, flange, clamp and purge-air adapter options. Assess conductive deposits, process temperature, pressure and Ex requirements together; confirm option compatibility using the order code.
Basis for technical values
The numerical values on this card are based on the downloadable manufacturer document MAN27 Rev.1. Process and ambient limits are assessed together for the standard or optional version ordered.
Output codes 01 and 20
| Code | Output / use |
| GM01 | Relay; threshold or flow/dust alarm |
| GM20 | 4–20 mA; relative change/trend monitoring |
Technical documents
dynaguard-gm technical information · English PDFDownload document ↓DYNAguard general brochure · English PDFDownload document ↓When is it suitable?
When early detection of filter damage or increased dust passage due to leakage is required.
Technical selection and configuration
| Measuring principle | Modified triboelectric / electrostatic particle detection |
| Supply | 17–31 VDC; relay version maximum 60 mA, analog version maximum 90 mA |
| Output | GM01 relay / GM20 active, galvanically isolated 4–20 mA |
| Relay / analog load | Max. 48 VAC/DC, 1 A / <500 Ω |
| Ambient temperature | −20…+70°C |
| Standard process | Up to +90°C / 6 bar |
| Process options | HT130: +130°C; HT200: +200°C; HT290: +290°C; pressure option 25 bar |
| Protection rating | Standard IP67; relevant marking governs Ex versions |
Confirm numeric limits and connection options against the current manufacturer datasheet and exact order code.
Installation notes
Select the downstream measurement point and sensor length according to duct geometry. Set signals considering normal filter operation and cleaning cycles.
ATEX and certificates
Assess the Ex zone and certification requirements together with manufacturer documentation for the selected variant. The product family name alone does not establish ATEX suitability.
What should I provide for technical selection?
Provide material name, particle size, moisture and density; minimum/normal/maximum capacity; conveying method, pipe or hose diameter, temperature, pressure and desired output. A mounting drawing helps selection.