A running feeder or fan alone does not prove product movement in the pipe. The flow sensor monitors material movement at the selected section to help detect feed interruption. Its information applies to that measuring point; it cannot alone locate or explain a line fault.
First decide whether you need flow/no-flow, relative flow changes or kg/h flow. A switch selected for interruption alarms is not expected to calculate total production.
Which sensor provides which information?
| Requirement | Product approach | Check point |
| Flow/no-flow | FS 510M or suitable DYNAguard K/P/V relay variant | Pipe and connection geometry, material, sensing principle |
| Flow in flexible hoses | DYNAguard S01; S20 for trends | Hose conductivity, diameter and T/E/W connection |
| Monitor flow trends in the PLC | FS 550M or DYNAguard analogue variant | The signal is a relative trend, not directly kg/h |
| kg/h and total quantity | MF 3001 / DYNA M-flow or DYNAmas | Application-suitable measurement and reference calibration |
Why does sensor location matter?
A sensor before or after a feeder answers different questions. To monitor one feeder's output, the measuring point must represent that flow. In a common line with several feeds, one sensor may not identify which feed stopped.
Rotary valve or flap motion may enter a microwave sensor's field. Assess metal-pipe connection, product impact, deposits and wear together with the selected device's installation instructions.
Filter time and alarm delay are different settings
Filter time smooths brief signal changes; relay delay affects switching time. Too short a setting can cause repeated alarms during normal pulsed flow; too long can delay detection of real interruptions. No single time value suits every plant.
FS 510M provides sensitivity, filter, hysteresis and delay settings. Observe normal and interrupted flow signals first, then adjust to the process response requirement. Assess sensor and PLC delays together.
Which conditions are tested during commissioning?
| State | Behavior to verify |
| Line running, product flowing | Stable normal state; correct detection even at low flow |
| Line running, product feed interrupted | No-flow alarm within the defined time |
| Normal intermittent feeding | Expected empty intervals do not cause false alarms |
| Startup and normal shutdown | Alarm evaluation consistent with operating sequence |
| Sensor power or connection lost | Defined fault behavior for the selected device and control system |
Information to send for technical assessment
Provide material name and particle size, minimum/normal/maximum capacity, pipe internal diameter and material, pressure, temperature, conveying method, feed cycle and required relay/analog output. Include a line sketch showing sensor position and photos of nearby valves and bends.
Catalogue drawings
Technical documents
| Industry | Powder and granule processing plants |
| Material | Powders, granules and pellets |
| Process | Feeder → pneumatic conveying line → receiver |
Problem and measurement challenge
Distinguish normal pulsed feeding from genuine flow interruption.
Technology selection
Assess line type, pipe diameter, material, normal flow continuity and permissible response time together.
Installation and technical notes
The monitored section must represent the feed point being controlled. Separately assess moving mechanical parts within the microwave sensing area.
Let us choose the product for your application together
Share a line or duct photo, material details and the required alarm or trend output.
Request a quote for this application →Sources
Does a no-flow alarm prove that the pipe is blocked?
No. The sensor evaluates material movement at its location. Empty feeders, interrupted supply or blockage are distinguished using other process information.
How is the alarm set for normal pulsed feeding?
Observe the normal cycle on site; jointly adjust filtering, hysteresis and relay/PLC delay to the accepted response time.