The motor is running. Is material actually flowing?

Independent material-flow monitoring and a PLC alarm scenario with DYNAguard K/P/S.

The motor is running. Is material actually flowing?

What is the problem?

The PLC motor-running signal reports motor status. If the feed hopper is empty, material bridges or conveying is interrupted, the motor can run without material passing through the line.

Which product addresses it?

DYNAguard K/P/S flow sensors monitor material movement at the selected measuring point, complementing motor status with a separate process signal. The PLC can raise an alarm when material movement disappears while flow is expected.

The motor is running. Is material actually flowing?
DYNAguard K: example of an inline flow indicator. Assess DYNAguard S separately for flexible-hose applications.
View the product →
  1. 1 · Motor-running feedback
  2. 2 · Material movement in the line
  3. 3 · PLC: compare with expected flow
Conceptual diagram, not a scaled installation drawing.

On-site check sequence

1 · Select the measuring point first. Monitor the line where material is expected to pass; sensor position determines which part of the process a fault indication can cover.

2 · Select the model for the pipe and material. Assess DYNAguard K/P for suitable pipe and mounting conditions, and DYNAguard S for non-conductive flexible hoses. Verify the exact model, diameter and connection against manufacturer documentation.

3 · Check startup and normal flow separately. Observe transit time from feed startup to the sensor. Set threshold and delay after normal-flow and no-flow trials. Do not copy a catalogue example delay into every process.

PLC monitoring logic

StateInterpretation and action
No conveying demandNo-flow alone is not a fault.
Startup period activeAllow material to reach the measuring point.
Flow expected + flow presentMaterial passage at this point is confirmed.
Flow expected + no flowAlarm after the defined delay; select any shutdown response for the process scenario.

What does flow present not tell you?

A flow/no-flow signal alone does not provide a kg/h value. A relative trend from an analogue variant is not automatically calibrated mass flow either. For quantity measurement, assess MF 3001 or DYNAmass against process conditions and calibration options.

The sensor indicates interrupted flow; it does not by itself diagnose an empty hopper, bridging or another conveying problem. Verify fault and signal-loss behaviour for the selected device and control circuit.