Compare flow/no-flow detection, relative flow trends and calibrated mass flow measurement: different information can be transmitted using the same 4–20 mA standard.

A flow trend shows relative increases or decreases in material movement; mass flow is the quantity of material passing per unit time. Both measurements can be sent to a PLC via 4–20 mA. The difference is the measured quantity and signal scaling, not the signal standard.

Quick response

  • A relay output generally indicates flow present/absent or an alarm.
  • 4–20 mA is a signal transmission standard; it does not identify what is being measured.
  • On a trend sensor, 4–20 mA can indicate relative flow such as low, normal or high.
  • On mass flow meters such as MF 3001 / DYNA M-flow and DYNAmas, 4–20 mA can be scaled to calibrated kg/h or t/h.
  • Trend and mass flow measurement may require different devices, installation and process conditions.
Illustrative simulation: Both systems can use a 4–20 mA output. In a trend device, the signal represents relative change; in a mass flow meter, it represents kg/h after calibration and scaling.

What is the fundamental difference between flow trend and mass flow?

In bulk solids processes, define the question first. A flow switch may suffice for “Is material flowing?” A relative trend signal can show “Has flow fallen below normal?” “How many kilograms pass per hour?” requires mass flow measurement.

Measurement objectiveTypical outputQuestion answeredTotal consumptionProduct families
Flow/no-flowRelay or switchingIs material moving?NoMOLLET FPS, FS 510M, DynaGuard M; DynaGuard K/P/S/V relay variants
Flow trendRelative value via 4–20 mAHas flow increased or decreased?NoFS 550M; DynaGuard K/P/S/V analog varyantlar
Mass flow ratekg/h or t/h scaled via 4–20 mAHow much product passes per unit time?Yes, with a suitable systemMF 3001 / DYNA M-flow, DYNAmas, DYNAchute

Product names support technical preselection. Confirm material, line, output and certification details before choosing the final model and variant.

Classify your measurement objective now

Compare flow present/absent, trend and mass flow requirements against material and line details.

What does a flow present/absent sensor indicate?

A flow switch detects whether moving material is present in its sensing area. It can provide an alarm or interlock when the feeder runs without product, a chute empties or flow stops in a conveying line. It does not measure conveyed mass.

Microwave detection

MÜTEC FS 510M and DYNAguard M can be considered for monitoring moving material with microwaves. If rotary valves, flaps or other moving parts are in the sensing area, the risk of a false interpretation must be assessed. MOLLET FPS can also be considered for flow present/absent; verify its measurement principle and variant against current manufacturer documents.

Electrostatic detection

DynaGuard K, P, S and V use the natural electric charge of moving particles. K is considered for small pipe diameters, P for local detection, S for flexible hoses, and V for larger cross-sections and different process connections.

Relay variants of DynaGuard can be chosen for flow present/absent, while analogue variants can indicate flow trends. K01, P01 and S01 have relay outputs; K20, P20 and S20 provide 4–20 mA trend output. Confirm the exact output variant of DynaGuard V by order code before purchase.

What does a 4–20 mA output represent?

4–20 mA is an analogue signal standard for transmitting measurements to a control system. It does not specify the measured quantity. Temperature, pressure, level, relative flow trend and calibrated mass flow can all use it. A reading of 12 mA at the PLC only becomes a meaningful process value if the device range and scaling are known.

For FS 550M and analogue DynaGuard K/P/S/V variants, 4–20 mA can indicate whether flow is falling, rising or fluctuating relative to a reference operating point. For MF 3001 / DYNA M-flow and DYNAmas, it can represent kg/h or t/h after commissioning and scaling for mass flow. Ask what quantity and range the 4–20 mA represents, not merely whether the device has such an output.

How is mass flow measured?

Mass flow is the mass of material passing per unit time. MF 3001 / DYNA M-flow evaluates changes in the frequency and amplitude of a microwave signal reflected by particles moving through a metal pipe. The manufacturer specifies pneumatic conveying and free-fall applications. Calibrate in the process against one or more reference flow rates.

DYNAmas (DYNAmass) measures material concentration and conveying velocity separately to calculate mass flow. This distinction matters when velocity changes. Assess exact pipe diameter, measuring range and expected performance against product, concentration, velocity and mounting cross-section.

01

Choose a reference

Use a weighed batch, an existing weighing system, or product collected and weighed over a defined period.

02

Record the conditions

Record product, line geometry, velocity, moisture and feeding behaviour along with calibration.

03

Match the data points

Compare the sensor signal with the verified amount of material passing at the same time.

04

Perform an independent check

Check again at an operating point that was not used for calibration.

How does DYNAchute work with non-dusty materials?

The patented DYNAchute combines weighing technology with contactless velocity measurement for free-falling, free-flowing bulk solids. Material passes through a calming section into the weighing chute. A load cell measures the force perpendicular to the chute, while two sensors determine velocity from transit time. Mass and velocity together yield mass flow.

The manufacturer's brochure positions the system for granules and similar free-flowing products; DYNAchute is not selected for powder. It states that product calibration is unnecessary, a typical installation has no moving measuring components, and system accuracy can reach 0.2% of final value. This is a catalogue figure: confirm flowability, vertical and vibration-free mounting, inlet geometry and operating range for each application.

Difference between DYNAchute and an impact plate

AspectDYNAchuteImpact plate
Measurement approachChute mass and separate velocity measurementProduct impact force on the plate
Effect of product velocityVelocity measured separatelyPart of the impact force
Product-property changesManufacturer states moisture, density, particle size and friction changes do not affect accuracyMaterial and impact behavior can affect results
CalibrationNo product calibration according to manufacturer brochureCalibration according to application and product
InstallationVertical vibration-free free fallControlled impact geometry required
Accuracy statementUp to 0.2% of full scale in the catalogueVerified for selected system and process

Important: The stated DYNAchute accuracy is not an unconditional guarantee for every plant. Final assessment depends on the manufacturer's application review, device configuration and acceptance procedure.

Which measurement approach suits which process?

Process / needPreselection and product cardDecisive selection condition
Pneumatic line · flow/no-flowMicrowave/electrostatic sensing; select diameter, material and connection together.
Pneumatic line · relative trend4–20 mA tracks flow changes, not calibrated kg/h.
Flexible hose · flow/no flow or trendSelect hose conductivity, inner/outer diameter and T/E/W connection, then relay or analog output.
Metal pipe · mass flowPneumatic conveying/free fall; product- and point-specific reference calibration.
Mass flow · separate velocity measurementConcentration and velocity assessed together. Use product datasheet for capacity and diameter.
Free-fall granules / pellets · mass flowFree-flowing non-powder product; check vertical layout, vibration and inlet geometry.
Open chute · material movementCheck rotary valves, flaps and moving parts in the sensing field.

Dilute-phase pneumatic conveying, dense phase and free fall do not share the same calibration conditions. Even if a measuring principle suits several lines, assess material velocity, concentration and distribution across the cross-section separately.

Two catalogue installation examples

Manufacturer dimension drawing of DYNAguard S standard T/E hose connections
DYNAguard S GB11, p. 2: standard T/E connections. Use the relevant drawing for W and Ex versions. Full datasheet (PDF) →
Manufacturer connection layout for DYNA M-flow sensor and evaluation unit
DYNA M-flow GB10, p. 2: sensor and evaluation unit. Product page and documents →

The drawings compare installation approaches. Before fabrication or installation, use the dimensioned drawing for the exact ordered variant.

Process information affecting selection

Flow/no-flow, trend or mass-flow objectivePneumatic, free fall, chute or hoseMinimum, normal and maximum capacityPipe internal diameter and section geometryParticle size and product distributionBulk density and concentrationMoisture and product-property changesConveying velocity and flow regimeTemperature and process pressureMoving equipment near the mounting pointRequired relay, analog or communication outputReference weighing and acceptance method

Suitable and unsuitable expectations

Suitable measurement objectives

  • Feed interruption or blockage alarm
  • Monitoring deviations from normal flow
  • Process control of dosing or production rate
  • Total quantity calculation with a suitable system
  • Contactless measurement in a closed line

Requires separate assessment

  • Expecting t/h without calibration
  • Using one curve for changing products
  • Irregular and intermittent flow
  • Custody-transfer weighing
  • No suitable measuring section

Common mistakes

Assuming every 4–20 mA output means t/h

Not verifying whether analog signals mean relative trend or calibrated mass flow.

Expecting total consumption from a flow switch

Presence/absence does not include transported mass.

Skipping on-site calibration

Engineering units are unreliable until microwave mass-flow signals are matched with reference quantities.

Using one setting for different products

Moisture, size, density and electrical-property changes can affect signals.

Treating line types alike

Velocity, concentration and distribution differ in pneumatic conveying and free fall.

Mounting too close to moving equipment

Rotary valves or flaps may appear as product movement to some microwave sensors.

Promising catalogue accuracy unconditionally

Read applicable device, product, operating and mounting conditions together.

Confusing commercial weighing and process measurement

Billing measurements require separate legal-metrology assessment.

Technical selection support from Infomak

Infomak combines manufacturer documentation with experience in bulk solids processes to help preselect a flow switch, trend sensor or mass flow system. We first classify the application using material, capacity, line diameter and installation photo; final configuration follows verification.

Frequently asked questions

What differs between a flow sensor and a mass flow meter?

A flow sensor tracks movement or relative change. A mass flow meter uses a suitable principle and calibration to determine mass per time in kg/h or t/h.

Can a 4–20 mA output carry kg/h or t/h?

Yes. MF 3001 / DYNA M-flow and DYNAmas can represent calibrated kg/h or t/h over 4–20 mA. Trend sensors use the same standard for relative levels; verify the scaled quantity first.

Can total consumption be calculated from a flow trend?

Integrating an uncalibrated relative trend does not give reliable consumption; small deviations accumulate. Use validated mass flow and regular reference checks.

Why calibrate a mass flow meter in the process?

Microwave signals depend on material, geometry, density, moisture and distribution. Match raw signals to weighed batches or suitable references to obtain kg/h.

How does DYNAchute differ from an impact plate?

Impact plates use force on the plate. DYNAchute separately evaluates chute product mass and non-contact velocity to calculate free-fall mass flow.

What checks are needed in ATEX zones?

Check zone classification, exact variant, nameplate, certificate, internal/external zones and mounting together. Final selection follows the explosion-protection document and current manufacturer certificate.